Property Address:
422 Willow Brook Rd.
Winchester, ky 40391
![]() |
| Date: 12/31/2007 | Time: 9:00 AM | Report ID: 0029 |
| Property: 422 Willow Brook Rd. Winchester, ky 40391 |
Customer: Mr. David Armsrong |
Real Estate Professional: Lanny Evans |
Comment Key or Definitions
The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.
Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.
Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.
Not Present (NP) = This item, component or unit is not in this home or building.
Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
| Age Of Home: Over 25 Years | Client Is Present: Yes | Radon Test: No |
| Water Test: No | Weather: Clear | Temperature: Below 60 |
| Rain in last 3 days: Yes |
| Viewed roof covering from: Walked roof | Roof-Type: Gable | Roof Covering: 3-Tab fiberglass |
| Chimney (exterior): Brick | Sky Light(s): None | Roof Ventilation: Gable vents Soffit Vents |
| Method used to observe attic: Walked | Roof Structure: 2 X 4 Rafters | Ceiling Structure: 2X4 |
| Attic info: Attic access | Attic Insulation: Blown R-19 or better |
| 1.0 | ROOF COVERINGS Comments: Repair or Replace | |
![]() |
The Roof shingles missing at the front of home. It should be replaced as soon as possible. A qualified person should repair or replace as needed.
|
| 1.1 | FLASHINGS Comments: Inspected |
| 1.2 | SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS Comments: Repair or Replace | |
![]() |
The chimney cap is cracked in various spots allowing water to penetrate the chimney.
|
| 1.3 | ROOF VENTILATION Comments: Repair or Replace |
![]() |
The roof covering has recently been replaced and more ventilation should be added to promote life expectancy. |
| 1.4 | ROOF DRAINAGE SYSTEMS (gutters and downspouts) Comments: Inspected |
| 1.5 | ROOF STRUCTURE AND ATTIC (Report leak signs or condensation) Comments: Repair or Replace | |||||
![]() |
The common board roofing sags , and is deteriorated . The roof sheathing needs to be replaced. This will involve shingles and flashing. I recommend a qualified contractor perform the work.
The roof sheathing is "blackened" and has fungi growth indicating moisture intrusion in areas. Signs of fungi growth indicate that moisture is entering inside the attic.. The ventilation should be increased at next roof replacement and I recommend ridge vents be installed next roof replacement.
|
| 1.6 | VENTILATION FANS AND THERMOSTATIC CONTROLS (ATTIC) Comments: Not Present |
| 1.7 | INSULATION IN ATTIC Comments: Inspected |
| 1.8 | VISIBLE ELECTRIC WIRING IN ATTIC Comments: Not Present |
| Siding Style: Brick | Siding Material: Brick veneer | Exterior Entry Doors: Wood Steel |
| Appurtenance: Covered porch Deck | Driveway: Concrete |
| 2.0 | WALL CLADDING FLASHING AND TRIM Comments: Inspected |
| 2.1 | DOORS (Exterior) Comments: Inspected |
| 2.2 | WINDOWS Comments: Inspected |
| 2.3 | DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES, PATIO/ COVER AND APPLICABLE RAILINGS Comments: Inspected |
| 2.4 | VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIO FLOOR, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building) Comments: Repair or Replace | |
![]() |
The concrete drive at the front of the home is deteriorated in areas. Some repairs have been made. I recommend further repair as desired.
|
| 2.5 | EAVES, SOFFITS AND FASCIAS Comments: Repair or Replace | |
![]() |
A gap between the fascia and roof sheathing exists which allows insects or bees to enter attic.
|
| 2.6 | PLUMBING WATER FAUCETS (hose bibs) Comments: Inspected |
| 2.7 | OUTLETS (exterior) Comments: Inspected |
| 2.8 | ADDITIONAL BUILDINGS ON PROPERTY Comments: Repair or Replace | |
![]() |
I did not inspect any additional buildings. I only inspected the main structure. Deficiencies may exist with these structures or building (s). Our company makes no representation to the condition of these structures or building (s). The building is up against the side of the house with the roof sloped toward the house. This is the likely cause of some of the moisture problems in the crawl space.
|
| Garage Door Type: One automatic | Garage Door Material: Wood | Auto-opener Manufacturer: LIFT-MASTER |
| 3.0 | GARAGE CEILINGS Comments: Inspected |
| 3.1 | GARAGE WALLS (INCLUDING FIREWALL SEPARATION) Comments: Inspected |
| 3.2 | GARAGE FLOOR Comments: Inspected |
| 3.3 | GARAGE DOOR (S) Comments: Inspected |
| 3.4 | OCCUPANT DOOR FROM GARAGE TO INSIDE HOME Comments: Not Present |
| 3.5 | GARAGE DOOR OPERATORS (Report whether or not doors will reverse when met with resistance) Comments: Inspected |
| Garage door functions as intended. |
| Dishwasher Brand: TAPPAN | Disposer Brand: IN SINK ERATOR | Exhaust/Range hood: KENMORE |
| Range/Oven: TAPPAN | Built in Microwave: NONE | Trash Compactors: NONE |
| Cabinetry: Laminate | Countertop: Laminate | Clothes Dryer Vent Material: Flexible Vinyl |
| Dryer Power Source: 220 Electric |
| 4.0 | CEILINGS Comments: Inspected |
| 4.1 | WALLS Comments: Inspected |
| 4.2 | FLOORS Comments: Inspected |
| 4.3 | PANTRY/CLOSET DOORS Comments: Not Present |
| 4.4 | WINDOWS Comments: Repair or Replace |
![]() |
The kitchen window above the sink would not open. |
| 4.5 | COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS Comments: Inspected |
| 4.6 | PLUMBING DRAIN AND VENT SYSTEMS Comments: Inspected |
| 4.7 | PLUMBING WATER SUPPLY FAUCETS AND FIXTURES Comments: Inspected |
| 4.8 | OUTLETS WALL SWITCHES and FIXTURES Comments: Inspected |
| 4.9 | DISHWASHER Comments: Inspected |
| 4.10 | RANGES/OVENS/COOKTOPS Comments: Inspected |
| 4.11 | RANGE HOOD Comments: Inspected |
| There was no light bulb in the range hood. Could not determine if it worked. |
| 4.12 | TRASH COMPACTOR Comments: Not Present |
| 4.13 | FOOD WASTE DISPOSER Comments: Repair or Replace |
![]() |
Disposer was locked up. |
| 4.14 | MICROWAVE COOKING EQUIPMENT Comments: Not Inspected |
| 4.15 | CLOTHES DRYER VENT PIPING Comments: Not Present |
| Ceiling Materials: Drywall | Wall Material: Drywall | Floor Covering(s): Carpet |
| Interior Doors: Hollow core | Window Types: Double-hung | Window Manufacturer: UNKNOWN |
| 5.0.A | CEILINGS Comments: Inspected |
| 5.1.A | WALLS Comments: Inspected |
| 5.2.A | FLOORS Comments: Inspected |
| 5.3.A | STEPS, STAIRWAYS, BALCONIES AND RAILINGS Comments: Not Present |
| 5.4.A | DOORS (REPRESENTATIVE NUMBER) Comments: Inspected |
| 5.5.A | WINDOWS (REPRESENTATIVE NUMBER) Comments: Inspected |
| 5.6.A | OUTLETS SWITCHES AND FIXTURES Comments: Inspected |
| Ceiling Materials: Drywall | Wall Material: Drywall | Floor Covering(s): Carpet |
| Interior Doors: Hollow core | Window Types: Double-hung | Window Manufacturer: UNKNOWN |
| 5.0.B | CEILINGS Comments: Inspected |
| 5.1.B | WALLS Comments: Inspected |
| 5.2.B | FLOORS Comments: Inspected |
| 5.3.B | STEPS, STAIRWAYS, BALCONIES AND RAILINGS Comments: Not Present |
| 5.4.B | DOORS (REPRESENTATIVE NUMBER) Comments: Inspected |
| 5.5.B | WINDOWS (REPRESENTATIVE NUMBER) Comments: Inspected |
| 5.6.B | OUTLETS SWITCHES AND FIXTURES Comments: Inspected |
| Ceiling Materials: Drywall | Wall Material: Drywall | Floor Covering(s): Carpet |
| Interior Doors: Hollow core | Window Types: Double-hung | Window Manufacturer: UNKNOWN |
| 5.0.C | CEILINGS Comments: Inspected |
| 5.1.C | WALLS Comments: Inspected |
| 5.2.C | FLOORS Comments: Inspected |
| 5.3.C | STEPS, STAIRWAYS, BALCONIES AND RAILINGS Comments: Not Present |
| 5.4.C | DOORS (REPRESENTATIVE NUMBER) Comments: Inspected |
| 5.5.C | WINDOWS (REPRESENTATIVE NUMBER) Comments: Inspected |
| 5.6.C | OUTLETS SWITCHES AND FIXTURES Comments: Inspected |
| Ceiling Materials: Drywall | Wall Material: Drywall | Floor Covering(s): Carpet |
| Interior Doors: Hollow core | Window Types: Double-hung | Window Manufacturer: UNKNOWN |
| 5.0.D | CEILINGS Comments: Inspected |
| 5.1.D | WALLS Comments: Inspected |
| 5.2.D | FLOORS Comments: Inspected |
| 5.3.D | STEPS, STAIRWAYS, BALCONIES AND RAILINGS Comments: Not Present |
| 5.4.D | DOORS (REPRESENTATIVE NUMBER) Comments: Inspected |
| 5.5.D | WINDOWS (REPRESENTATIVE NUMBER) Comments: Inspected |
| 5.6.D | OUTLETS SWITCHES AND FIXTURES Comments: Inspected |
| Ceiling Materials: Drywall | Wall Material: Drywall | Floor Covering(s): Carpet |
| Interior Doors: Wood | Window Types: Double-hung | Window Manufacturer: UNKNOWN |
| 5.0.E | CEILINGS Comments: Inspected |
| 5.1.E | WALLS Comments: Inspected |
| 5.2.E | FLOORS Comments: Inspected |
| 5.3.E | STEPS, STAIRWAYS, BALCONIES AND RAILINGS Comments: Not Present |
| 5.4.E | DOORS (REPRESENTATIVE NUMBER) Comments: Inspected |
| 5.5.E | WINDOWS (REPRESENTATIVE NUMBER) Comments: Inspected |
| 5.6.E | OUTLETS SWITCHES AND FIXTURES Comments: Repair or Replace | ||||
![]() |
One "three-prong" outlet is not working . Further inspection is needed by a qualified licensed electrician. A qualified licensed electrician should perform repairs that involve wiring.( Picture 1 )
The attic above the enclosed patio also had exposed wiring. This is a safety hazard and a qualified licensed electrician should perform repairs.( Picture 2 ) ( Picture 3 ) . There is also moisture in the attic above the Patio. There is no ventilation in the attic there.( Picture 4 )
|
| Exhaust Fans: Fan only |
| 6.0.A | COUNTERS AND CABINETS Comments: Inspected |
| 6.1.A | DOORS (REPRESENTATIVE NUMBER) Comments: Inspected |
| 6.2.A | WINDOWS Comments: Not Present |
| 6.3.A | PLUMBING DRAIN, WASTE AND VENT SYSTEMS Comments: Repair or Replace | ||
![]() |
The stop-valve does not work properly at the Hall Bath sink. Repairs are needed. A qualified person should repair as necessary.
|
| 6.4.A | PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES Comments: Inspected |
| 6.5.A | OUTLETS SWITCHES AND FIXTURES Comments: Inspected |
| 6.6.A | EXHAUST FAN Comments: Repair or Replace | |
![]() |
The Exhaust fan does not vent to outside at the hall bath. Vent pipes that terminate in attic space can sometimes cause moisture that can lead to mold or cause condensation. A qualified person should repair or replace as needed.
|
| Exhaust Fans: Fan only |
| 6.0.B | COUNTERS AND CABINETS Comments: Inspected |
| 6.1.B | DOORS (REPRESENTATIVE NUMBER) Comments: Inspected |
| 6.2.B | WINDOWS Comments: Not Present |
| 6.3.B | PLUMBING DRAIN, WASTE AND VENT SYSTEMS Comments: Inspected |
| 6.4.B | PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES Comments: Inspected |
| 6.5.B | OUTLETS SWITCHES AND FIXTURES Comments: Repair or Replace |
![]() |
The breaker for the fan, mirror and ceiling light in the master bath was tripped at time of inspection. A qualified electrician should inspect for further repairs. |
| 6.6.B | EXHAUST FAN Comments: Repair or Replace | |
![]() |
The Exhaust fan does not vent to outside at the master bath. Vent pipes that terminate in attic space can sometimes cause moisture that can lead to mold or cause condensation. A qualified person should repair or replace as needed.
|
| Foundation: Masonry block | Method used to observe Crawlspace: Crawled | Floor Structure: 2 X 10 |
| Wall Structure: Masonry | Columns or Piers: Masonry block | Floor System Insulation: NONE |
| 7.0 | FOUNDATIONS, BASEMENTS AND CRAWLSPACES (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.) Comments: Repair or Replace | |||||
![]() |
Visible signs of water intrusion in the crawlspace are present from water stains on walls and ground . ( Picture 1 ) ( Picture 2 )
There is also some deteriorated wood along the west wall at the back of the house.( Picture 3 ) ( Picture 4 ) Water intrusion if not corrected can lead to other problems including mold and cause excessive moisture to floor system that can lead to deterioration and increased repair cost.. I recommend further investigation or correction by a qualified licensed contractor or water infiltration specialist. The dryer vent terminates in the crawlspace. This also adds to the moisture problem.( Picture 5 )
|
| 7.1 | WALLS (Structural) Comments: Inspected |
| 7.2 | COLUMNS OR PIERS Comments: Inspected |
| 7.3 | FLOORS (Structural) Comments: Inspected |
| 7.4 | CEILINGS (structural) Comments: Inspected |
| 7.5 | INSULATION UNDER FLOOR SYSTEM Comments: Repair or Replace |
![]() |
The floor system is not insulated. Heat loss can occur more on this home than one that is properly insulated. |
| 7.6 | VAPOR RETARDERS (ON GROUND IN CRAWLSPACE OR BASEMENT) Comments: Repair or Replace |
![]() |
The vapor barrier (plastic) on the crawlspace ground is missing. A vapor barrier provides added protection to the floor system from moisture or dampness that can enter from ground. A qualified person should repair or replace as needed. |
| 7.7 | VENTILATION OF FOUNDATION AREA (crawlspace or basement) Comments: Repair or Replace |
![]() |
The crawlspace does not have sufficient ventilation. Lack of ventilation can cause moisture in the crawlspace. A qualified contractor should inspect for further repairs. |
| Water Source: Public | Water Filters: None | Plumbing Water Supply (into home): Copper |
| Plumbing Water Distribution (inside home): Copper | Washer Drain Size: 2" Diameter | Plumbing Waste Line: ABS |
| Water Heater Power Source: Gas (quick recovery) | Water Heater Capacity: 50 Gallon (2-3 people) | Water Heater Manufacturer: A.O. SMITH |
| 8.0 | PLUMBING DRAIN, WASTE AND VENT SYSTEMS Comments: Inspected |
| 8.1 | PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES Comments: Inspected |
| 8.2 | HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS Comments: Inspected |
| 8.3 | MAIN WATER SHUT-OFF DEVICE (Describe location) Comments: Inspected | |
![]() |
The main shut off is the blue knob located underneath in the crawlspace. This is for your information.
|
| 8.4 | FUEL STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting, supports, leaks) Comments: Not Present |
| 8.5 | MAIN FUEL SHUT OFF (Describe Location) Comments: Inspected |
| 8.6 | SUMP PUMP Comments: Not Present |
| Electrical Service Conductors: Overhead service 220 volts | Panel capacity: 200 AMP | Panel Type: Circuit breakers |
| Electric Panel Manufacturer: GENERAL ELECTRIC | Branch wire 15 and 20 AMP: Copper | Wiring Methods: Romex |
| 9.0 | SERVICE ENTRANCE CONDUCTORS Comments: Inspected |
| 9.1 | SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS Comments: Inspected |
| 9.2 | BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE Comments: Inspected |
| 9.3 | CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls) Comments: Inspected |
| 9.4 | POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE Comments: Inspected |
| 9.5 | OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS) Comments: Inspected |
| 9.6 | LOCATION OF MAIN AND DISTRIBUTION PANELS Comments: Inspected |
![]() |
The main panel box is located at the laundry room. |
| 9.7 | SMOKE DETECTORS Comments: Not Present |
| 9.8 | CARBON MONOXIDE DETECTORS Comments: Not Present |
| Heat Type: Forced Air | Energy Source: Gas | Number of Heat Systems (excluding wood): One |
| Heat System Brand: TRANE | Ductwork: Insulated | Filter Type: Disposable |
| Types of Fireplaces: Vented gas logs | Operable Fireplaces: One | Number of Woodstoves: None |
| Cooling Equipment Type: Air conditioner unit | Cooling Equipment Energy Source: Electricity | Central Air Manufacturer: TRANE |
| Number of AC Only Units: One |
| 10.0 | HEATING EQUIPMENT Comments: Inspected |
| 10.1 | NORMAL OPERATING CONTROLS Comments: Inspected |
| 10.2 | AUTOMATIC SAFETY CONTROLS Comments: Inspected |
| 10.3 | DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors) Comments: Inspected |
| 10.4 | PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM Comments: Inspected |
| 10.5 | CHIMNEYS, FLUES AND VENTS (for fireplaces, gas water heaters or heat systems) Comments: Inspected |
| The liner was partially visible and appeared good, but due to creosote build-up we could not inspect for cracks. I recommend a licensed chimney sweep clean and inspect for safety. |
| 10.6 | SOLID FUEL HEATING DEVICES (Fireplaces, Woodstove) Comments: Repair or Replace | |
![]() |
The mortar for the Fire-bricks in the fireplace at the Living room is deteriorated and inadequate repairs have been made. This burn area should be fireproof. Any repairs should be performed according to the manufacturer's specifications.
|
| 10.7 | COOLING AND AIR HANDLER EQUIPMENT Comments: Not Inspected |
| The A/C was not tested for proper operation due to the outside air temperature is 65 degrees or less. We did not inspect this unit(s). |
| 10.8 | NORMAL OPERATING CONTROLS Comments: Inspected |
| 10.9 | PRESENCE OF INSTALLED COOLING SOURCE IN EACH ROOM Comments: Not Inspected |
![]() 4 Keyse Property Inspections
210 Atwood Dr. |
Customer |
Property Address |
| 1.0 | ROOF COVERINGS | |
| Repair or Replace | ||
![]() |
The Roof shingles missing at the front of home. It should be replaced as soon as possible. A qualified person should repair or replace as needed. |
|
| 1.2 | SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS | |
| Repair or Replace | ||
![]() |
The chimney cap is cracked in various spots allowing water to penetrate the chimney. |
|
| 1.3 | ROOF VENTILATION | |
| Repair or Replace | ||
![]() |
The roof covering has recently been replaced and more ventilation should be added to promote life expectancy. |
|
| 1.5 | ROOF STRUCTURE AND ATTIC (Report leak signs or condensation) | |
| Repair or Replace | ||
![]() |
The common board roofing sags , and is deteriorated . The roof sheathing needs to be replaced. This will involve shingles and flashing. I recommend a qualified contractor perform the work.
The roof sheathing is "blackened" and has fungi growth indicating moisture intrusion in areas. Signs of fungi growth indicate that moisture is entering inside the attic.. The ventilation should be increased at next roof replacement and I recommend ridge vents be installed next roof replacement. |
|
| 2.4 | VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIO FLOOR, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building) | |
| Repair or Replace | ||
![]() |
The concrete drive at the front of the home is deteriorated in areas. Some repairs have been made. I recommend further repair as desired. |
|
| 2.5 | EAVES, SOFFITS AND FASCIAS | |
| Repair or Replace | ||
![]() |
A gap between the fascia and roof sheathing exists which allows insects or bees to enter attic. |
|
| 2.8 | ADDITIONAL BUILDINGS ON PROPERTY | |
| Repair or Replace | ||
![]() |
I did not inspect any additional buildings. I only inspected the main structure. Deficiencies may exist with these structures or building (s). Our company makes no representation to the condition of these structures or building (s). The building is up against the side of the house with the roof sloped toward the house. This is the likely cause of some of the moisture problems in the crawl space. |
|
| 4.4 | WINDOWS | |
| Repair or Replace | ||
![]() |
The kitchen window above the sink would not open. |
|
| 4.13 | FOOD WASTE DISPOSER | |
| Repair or Replace | ||
![]() |
Disposer was locked up. |
|
| 5.6.E | OUTLETS SWITCHES AND FIXTURES | |
| Repair or Replace | ||
![]() |
One "three-prong" outlet is not working . Further inspection is needed by a qualified licensed electrician. A qualified licensed electrician should perform repairs that involve wiring.( Picture 1 )
The attic above the enclosed patio also had exposed wiring. This is a safety hazard and a qualified licensed electrician should perform repairs.( Picture 2 ) ( Picture 3 ) . There is also moisture in the attic above the Patio. There is no ventilation in the attic there.( Picture 4 ) |
|
| 6.3.A | PLUMBING DRAIN, WASTE AND VENT SYSTEMS | |
| Repair or Replace | ||
![]() |
The stop-valve does not work properly at the Hall Bath sink. Repairs are needed. A qualified person should repair as necessary. |
|
| 6.6.A | EXHAUST FAN | |
| Repair or Replace | ||
![]() |
The Exhaust fan does not vent to outside at the hall bath. Vent pipes that terminate in attic space can sometimes cause moisture that can lead to mold or cause condensation. A qualified person should repair or replace as needed. |
|
| 6.5.B | OUTLETS SWITCHES AND FIXTURES | |
| Repair or Replace | ||
![]() |
The breaker for the fan, mirror and ceiling light in the master bath was tripped at time of inspection. A qualified electrician should inspect for further repairs. |
|
| 6.6.B | EXHAUST FAN | |
| Repair or Replace | ||
![]() |
The Exhaust fan does not vent to outside at the master bath. Vent pipes that terminate in attic space can sometimes cause moisture that can lead to mold or cause condensation. A qualified person should repair or replace as needed. |
|
| 7.0 | FOUNDATIONS, BASEMENTS AND CRAWLSPACES (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.) | |
| Repair or Replace | ||
![]() |
Visible signs of water intrusion in the crawlspace are present from water stains on walls and ground . ( Picture 1 ) ( Picture 2 )
There is also some deteriorated wood along the west wall at the back of the house.( Picture 3 ) ( Picture 4 ) Water intrusion if not corrected can lead to other problems including mold and cause excessive moisture to floor system that can lead to deterioration and increased repair cost.. I recommend further investigation or correction by a qualified licensed contractor or water infiltration specialist. The dryer vent terminates in the crawlspace. This also adds to the moisture problem.( Picture 5 ) |
|
| 7.5 | INSULATION UNDER FLOOR SYSTEM | |
| Repair or Replace | ||
![]() |
The floor system is not insulated. Heat loss can occur more on this home than one that is properly insulated. |
|
| 7.6 | VAPOR RETARDERS (ON GROUND IN CRAWLSPACE OR BASEMENT) | |
| Repair or Replace | ||
![]() |
The vapor barrier (plastic) on the crawlspace ground is missing. A vapor barrier provides added protection to the floor system from moisture or dampness that can enter from ground. A qualified person should repair or replace as needed. |
|
| 7.7 | VENTILATION OF FOUNDATION AREA (crawlspace or basement) | |
| Repair or Replace | ||
![]() |
The crawlspace does not have sufficient ventilation. Lack of ventilation can cause moisture in the crawlspace. A qualified contractor should inspect for further repairs. |
|
| 8.3 | MAIN WATER SHUT-OFF DEVICE (Describe location) | |
| Inspected | ||
![]() |
The main shut off is the blue knob located underneath in the crawlspace. This is for your information. |
|
| 9.6 | LOCATION OF MAIN AND DISTRIBUTION PANELS | |
| Inspected | ||
![]() |
The main panel box is located at the laundry room. |
|
| 10.6 | SOLID FUEL HEATING DEVICES (Fireplaces, Woodstove) | |
| Repair or Replace | ||
![]() |
The mortar for the Fire-bricks in the fireplace at the Living room is deteriorated and inadequate repairs have been made. This burn area should be fireproof. Any repairs should be performed according to the manufacturer's specifications. |
|
Prepared Using HomeGauge http://www.homegauge.com SHGI (c) 2000-2004 : Licensed To 4 Keyse Property Inspections
|
INVOICE |
| 4 Keyse Property Inspections
210 Atwood Dr. Georgetown, Ky 40324 Inspected By: Gene Keyse |
Inspection Date: 12/31/2007
Report ID: 0029 |
| Customer Info: | Inspection Property: |
| Mr. David Armsrong
300 Bellmont Ave. Winchester ky 40391 Customer's Real Estate Professional: Lanny Evans |
422 Willow Brook Rd. Winchester, ky 40391 |
Inspection Fee:
| ||||||||||||||||
Tax $0.00 | ||||||||||||||||
| Total Price $300.00 |
Payment Method: Check
Payment Status: Paid
Note: 12-31-07 Check # 4914